Reactive, and Apparent power



Reactive, and Apparent power

We know that reactive loads such as inductors and capacitors dissipate zero power, yet the fact that they drop voltage and draw current gives the deceptive impression that they actually do dissipate power. This “phantom power” is called reactive power, and it is measured in a unit called Volt-Amps-Reactive (VAR), rather than watts. The mathematical symbol for reactive power is (unfortunately) the capital letter Q. The actual amount of power being used, or dissipated, in a circuit is called true power, and it is measured in watts (symbolized by the capital letter P, as always). The combination of reactive power and true power is called apparent power, and it is the product of a circuit's voltage and current, without reference to phase angle. Apparent power is measured in the unit of Volt-Amps (VA) and is symbolized by the capital letter S.
As a rule, true power is a function of a circuit's dissipative elements, usually resistances (R). Reactive power is a function of a circuit's reactance (X). Apparent power is a function of a circuit's total impedance (Z). Since we're dealing with scalar quantities for power calculation, any complex starting quantities such as voltage, current, and impedance must be represented by their polar magnitudes, not by real or imaginary rectangular components. For instance, if I'm calculating true power from current and resistance, I must use the polar magnitude for current, and not merely the “real” or “imaginary” portion of the current. If I'm calculating apparent power from voltage and impedance, both of these formerly complex quantities must be reduced to their polar magnitudes for the scalar arithmetic.
There are several power equations relating the three types of power to resistance, reactance, and impedance (all using scalar quantities):

Please note that there are two equations each for the calculation of true and reactive power. There are three equations available for the calculation of apparent power, P=IE being useful only for that purpose. Examine the following circuits and see how these three types of power interrelate for: a purely resistive load in Figure below, a purely reactive load in Figure below, and a resistive/reactive load in Figure below.
Resistive load only:
True power, reactive power, and apparent power for a purely resistive load.
Reactive load only:
True power, reactive power, and apparent power for a purely reactive load.
Resistive/reactive load:
True power, reactive power, and apparent power for a resistive/reactive load.
These three types of power -- true, reactive, and apparent -- relate to one another in trigonometric form. We call this the power triangle: (Figure below).
Power triangle relating appearant power to true power and reactive power.
Using the laws of trigonometry, we can solve for the length of any side (amount of any type of power), given the lengths of the other two sides, or the length of one side and an angle.

  • Digg
  • Del.icio.us
  • StumbleUpon
  • Reddit
  • RSS
Read Comments

Power in resistive and reactive AC circuits


Power in resistive and reactive AC circuits


 

For comparison, let's consider a simple AC circuit with a purely reactive load in Figure  below.
simple AC circuit
AC circuit with a purely reactive (inductive) load.




Power is not dissipated in a purely reactive load. Though it is alternately absorbed from and returned to the source.
Note that the power alternates equally between cycles of positive and negative. (Figure above ) This means that power is being alternately absorbed from and returned to the source. If the source were a mechanical generator, it would take (practically) no net mechanical energy to turn the shaft, because no power would be used by the load. The generator shaft would be easy to spin, and the inductor would not become warm as a resistor would.
Now, let's consider an AC circuit with a load consisting of both inductance and resistance in Figure blow.
AC circuit with a load consisting of both inductance and resistance      
AC circuit with both reactance and resistance.


At a frequency of 60 Hz, the 160 millihenrys of inductance gives us 60.319 Ω of inductive reactance. This reactance combines with the 60 Ω of resistance to form a total load impedance of 60 + j60.319 Ω, or 85.078 Ω ∠ 45.152o. If we're not concerned with phase angles (which we're not at this point), we may calculate current in the circuit by taking the polar magnitude of the voltage source (120 volts) and dividing it by the polar magnitude of the impedance (85.078 Ω). With a power supply voltage of 120 volts RMS, our load current is 1.410 amps. This is the figure an RMS ammeter would indicate if connected in series with the resistor and inductor.
We already know that reactive components dissipate zero power, as they equally absorb power from, and return power to, the rest of the circuit. Therefore, any inductive reactance in this load will likewise dissipate zero power. The only thing left to dissipate power here is the resistive portion of the load impedance. If we look at the waveform plot of voltage, current, and total power for this circuit, we see how this combination works in Figure below.
A combined resistive/reactive circuit dissipates more power than it returns to the source. The reactance dissipates no power; though, the resistor does.
As with any reactive circuit, the power alternates between positive and negative instantaneous values over time. In a purely reactive circuit that alternation between positive and negative power is equally divided, resulting in a net power dissipation of zero. However, in circuits with mixed resistance and reactance like this one, the power waveform will still alternate between positive and negative, but the amount of positive power will exceed the amount of negative power. In other words, the combined inductive/resistive load will consume more power than it returns back to the source.
Looking at the waveform plot for power, it should be evident that the wave spends more time on the positive side of the center line than on the negative, indicating that there is more power absorbed by the load than there is returned to the circuit. What little returning of power that occurs is due to the reactance; the imbalance of positive versus negative power is due to the resistance as it dissipates energy outside of the circuit (usually in the form of heat). If the source were a mechanical generator, the amount of mechanical energy needed to turn the shaft would be the amount of power averaged between the positive and negative power cycles.
Mathematically representing power in an AC circuit is a challenge, because the power wave isn't at the same frequency as voltage or current. Furthermore, the phase angle for power means something quite different from the phase angle for either voltage or current. Whereas the angle for voltage or current represents a relative shift in timing between two waves, the phase angle for power represents a ratio between power dissipated and power returned. Because of this way in which AC power differs from AC voltage or current, it is actually easier to arrive at figures for power by calculating with scalar quantities of voltage, current, resistance, and reactance than it is to try to derive it from vector, or complex quantities of voltage, current, and impedance that we've worked with so far.

 

  • Digg
  • Del.icio.us
  • StumbleUpon
  • Reddit
  • RSS
Read Comments

Methods of cable installation


Methods of cable installation


We have seen that the rating of a cable depends on its ability to lose the heat produced in it by the current it carries and this depends to some extent on the way the cable is installed. A cable clipped to a surface will more easily be able to dissipate heat than a similar cable which is installed with others in a conduit,
 lists twenty standard methods of installation, each of them taken into account in the rating tables of the same Appendix. For example, two 2.5 mm² single core p.v.c. insulated non-armoured cables drawn into a steel conduit (installation method 3) have a current rating of 24 A  A 2.5 mm² twin p.v.c. insulated and sheathed cable, which contains exactly the same conductors, has a current rating of 27 A  when clipped directly to anon-metallic surface. Cables sheathed in p.v.c. must not be subjected to direct sunlight, because the ultra-violet component will leach out the plasticiser, causing the sheath to harden and crack. Cables must not be run in the same enclosure (e.g. trunking, pipe or ducting) as non-electrical services such as water, gas, air, etc. unless it has been established that the electrical system can suffer no harm as a result. If electrical and other services have metal sheaths and are touching, they must be bonded. Cables must not be run in positions where they may suffer or cause damage or interference with other systems. They should not, for example, be run alongside hot pipes or share a space with a hearing induction loop.
Special precautions may need to be taken where cables or equipment are subject to ionising radiation. Where a wiring system penetrates a load bearing part of a building construction it must he ensured that the penetration will not adversely affect the integrity of the construction.
The build-up of dust on cables can act as thermal insulation. In some circumstances the dust may be flammable or even explosive. Design cable runs to minimise dust accumulation: run cables on vertically mounted cable ladders rather than horizontal cable trays. When cables are run together, each sets up a magnetic field with a strength depending on the current carried. This field surrounds other cables, so that there is the situation of current-carrying conductors situated in a magnetic field. This will result in a force on the conductor, which is usually negligible under normal conditions but which can become very high indeed when heavy currents flow under fault conditions. All cables and conductors must be properly fixed or supported to prevent damage to them under these conditions.